SP/T6 - 6-channel temperature protection and diagnostics module

Temperature control module SP/T6 is a 6-channel module which supports inputs for connection of thermocouples and resistant thermometers as well as 6 current outputs of slowly varying 4-20mA signal value DA-converter.
Four relay (RELAY) SP/T6 modules are programmed for special alarm set points for one or several channels.
Specifications
SP/T6 specification:
№ | Feature | Measuring units | Value |
1. | Number of measuring channels | - | 6 |
2. | Thermocouples voltage measuring range | mV | from -25 to +75 |
3. | Thermal resistors resistance measuring range | Оhm | from 10 to 400 |
4. | Thermal resistors supply current: | ||
- in 4-wire scheme | mА | 0,25 or 1 | |
- in 3-wire scheme | mА | 0,25 or 0,75 | |
5. | Basic reduced measuring error of DC voltage (data acquisition frequency is 100 Hz) | % | ±0,03 |
6. | Basic reduced measuring error of thermal resistors resistance (data acquisition frequency is 100 Hz) | % | ±0,03 |
7. | Number of 4-20 mA outputs of slowly varying signal | - | 6 |
8. | Slowly varying signal 4-20 mA output current range | mА | from 2 to 24 |
9. | The maximum load resistance of each output value of the slowly varying signal | Оhm | 900 |
10. | Number of independent relay outputs | - | 4 |
11. | SP/T6 modules response time (from signal input to relay output), max | ms | 100 |
12. | Temperature modules response time (from signal input voltage to relay outputs), max | sec | 1 |
13. | Cold end measuring heat sensor measuring range | °С | -40…+150 |
14. | Cold end measuring heat sensor error | °С | ±1 |
15. | PHY of data transmission to other modules in a crate via maid data transmission interface | - | 100 Mbit/s |
16. | Maximum number of modules in a crate with which SP/T6 can simultaneously support main data processing interface | - | 6 |
17. | Power consumption, max | W | 6 |
Input primary transducers (sensors) |
|||
№ | Sensor | Measuring range, °C | Statistical characteristic, according to standard: |
1. | Thermocouple type E | ?200...+900 | GOST R 8.585-2001 «National measurement assurance system. Thermocouples» |
2. | Thermocouple type J | -40...+900 | GOST R 8.585-2001 National measurement assurance system. |
3. | Thermocouple type K | -250...+1300 | GOST R 8.585-2001 National measurement assurance system. |
4. | Thermocouple type T | -200...+400 | GOST R 8.585-2001 National measurement assurance system. |
5. | Thermocouple type L | -40...+900 | GOST R 8.585-2001 National measurement assurance system. |
6. | Thermal transducer type М: 100 Оhm, ? =0.00428 | -180...+200 | GOST 6651-2009 «National measurement assurance system. Thermal transducers» |
7. | Thermal transducer type Н: 120 Оhm, ? =0.00617 | -60...+100 | GOST 6651-2009 |
8. | Thermal transducer type Pt: 100 Оhm, ? =0.00385 | -200...+850 | GOST 6651-2009 |