SP/IO8 - 8-channel comprehensive module

The module has 8 comprehensive channels for analog input of unified voltage and current signals and 8 channels for analog output of current signals. Comprehensive SP/IO8 module can be applied for extending the number of channels of SP/V4 and SP/T6 modules by including more than one module into one protection contour with admissible decrease in fault-tolerance.
Thus, using SP/IO8 module is a compromise between the cost of the system and its fault-tolerance.
Specifications
SP/IO8 specification:
№ | Feature | Measuring units | Value |
1. | Number of measuring channels | - | 8 |
2. | Voltage measuring range | V |
from 0 to +1 from 0 to +10 from 0 to +20 |
3. | Current measuring range | mA | from 0 to 20 |
4. | Input impedance of input voltage, min | mOhm | 1 |
5. | Input impedance of current measurement input | Ohm | 150-200 |
6. | Relative error of channels set point | % | ±1 |
7. | Number of DA converter parallel channels 4-20 mA сwith current output | - | 8 |
8. | DA converter channels output range | mA | from 2 to 24 |
9. | Maximum load resistance of d-a converter | Ohm | 900 |
10. | Galvanic isolation of AD converter channels | - | Local |
11. | Galvanic isolation of DA converter channels | - | In groups of 4 channels |
12. | Number of HART-modem controllers | - | 2 |
13. | Power consumption, min | W | 5 |