VTEM skitter

EQUIPMENT

OUR COMPANY IS THE MANUFACTURER OF A COMPREHENSIVE MONITORING AND DIAGNOSTICS SYSTEM КD2210 FOR EVALUATION OF THE TECHNICAL CONDITION OF PUMP AND COMPRESSOR EQUIPMENT

SP/IO8 - 8-channel comprehensive module

SP-IO8The module has 8 comprehensive channels for analog input of unified voltage and current signals and 8 channels for analog output of current signals. Comprehensive SP/IO8 module can be applied for extending the number of channels of SP/V4 and SP/T6 modules by including more than one module into one protection contour with admissible decrease in fault-tolerance.

Thus, using SP/IO8 module is a compromise between the cost of the system and its fault-tolerance.

 

 

 

 

 

 

SP/IO8 specification:

 №  Feature   Measuring units    Value  
1.  Number of measuring channels  -  8
2.  Voltage measuring range  V  from 0 to +1
from 0 to +10
from 0 to +20
3.  Current measuring range  mA  from 0 to 20
4.  Input impedance of input voltage, min  mOhm  1
5.  Input impedance of current measurement input   Ohm  150-200
6.  Relative error of channels set point  %  ±1
7.  Number of DA converter parallel channels 4-20 mA сwith current output  -  8
8.  DA converter channels output range  mA  from 2 to 24
9.  Maximum load resistance of d-a converter  Ohm  900
10.  Galvanic isolation of AD converter channels   -  Local
11.  Galvanic isolation of DA converter channels  -  In groups of 4 channels
12.  Number of HART-modem controllers  -  2
13.  Power consumption, min  W  5